Start with everything in the raceway
Enter every insulated conductor for fill. Then determine which conductors count for ampacity adjustment from the actual circuit arrangement. Do not count only the hot wires by habit.
Grounds and neutrals are different
Equipment grounding and bonding conductors do not count toward current-carrying adjustment. An insulated equipment ground still takes up physical space.
A neutral that carries only the imbalance from other conductors of the same circuit may be excluded under the applicable rule. Other neutrals count; nonlinear loads and particular multiwire arrangements need attention. PassPull does not infer this from a conductor’s role or quantity.
| Conductor | Counts for fill? | Counts for adjustment? |
|---|---|---|
| Line conductor carrying load | Yes | Yes |
| Neutral of an independent two-wire circuit | Yes | Yes |
| Neutral carrying only the imbalance of the same circuit | Yes | May be excluded under 310.15(E)(1) |
| Insulated equipment ground | Yes | No · 310.15(F) |
A simple count example
Three independent two-wire line-to-neutral circuits have six current-carrying conductors: three line conductors and three load-carrying neutrals. Add one appropriately selected insulated equipment ground and the physical fill count is seven. The adjustment count remains six.
That example is not a rule for all three-circuit arrangements. A shared-neutral configuration can require a different count. Confirm the configuration before using an exclusion.
What changes at four, seven and ten conductors?
Use the verified current-carrying count, rather than the total physical wire count, to select the adjustment factor. Ambient-temperature correction and termination limits still apply separately. These are the first adjustment bands for standard runs within the checker’s scope.
For example, 12 AWG copper THHN/THWN-2 starts at 30 A in the 90°C column. At 30°C ambient, nine current-carrying conductors give 30 A × 70% = 21 A before the terminal ceiling; ten give 30 A × 50% = 15 A. That change can matter even when the conduit has plenty of space.
| Current-carrying conductors | Ampacity factor |
|---|---|
| 1–3 | 100% |
| 4–6 | 80% |
| 7–9 | 70% |
| 10–20 | 50% |
Check the source
Use NEC 2023 310.15(E) and (F) for neutral and grounding-conductor treatment, and Table 310.15(C)(1) for the adjustment factor. If you cannot establish the correct count, the result is not ready to rely on.